Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T19CM02007

Parcel: 123020340


Addresses:

2843 E EDISON ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/25/2019 FRAMING Approved
07/19/2019 FRAMING Partial Approval Sheathing not properly nailed, missing anchor bolts on exterior walls and interior walls
07/18/2019 FRAMING Not ready for Inspection Too many items to list beyond previous inspection results, walked project with builder,Recall when all issues have been addressed.
07/17/2019 FRAMING Denied 1- Plumbing is incomplete.
2- Shall seal the top plate electric conductors penetrations with fire rated foam or caulk.
3- Shall provide (3) sided blocking for all forced air vents.
4- Shall remove the fernco coupling located at the front South East wall and provide a mission specialty coupling.
5- Shall provide a minimum of 12 inches of separation of the water lines to the can lights.