Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T19CM01873
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/13/2019 | FIRE - FINAL | Approved | ||
09/06/2019 | FIRE - FINAL | Partial Approval | Okay for TCO to move in equipment and furniture. Re-inspection fee added. See alarm and sprinkler notes. FDC sign needed on second FDC connection on the east side. Also shall have signs indicating what portion of the building is protected "East" and "West." All Electrical shall be covered or functioning. Need an Annual and 5 year check valve complete. |
|
09/05/2019 | FIRE - FINAL | Partial Approval | Checked the emergency and exit lights Need to add on light middle of the southern hall One light needs to be moved to a better position so that you do not exit through a wall Need a FACP Inside sign FDC sign Need suite numbers on the exterior doors Need red lock out for the fire alarm system |