Inspection History: FIRE - FINAL
Permit Number - T19CM01772
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/21/2019 | FIRE - FINAL | Approved | added em light over rear door. | |
06/14/2019 | FIRE - FINAL | Partial Approval | OK for temp C of O. Call in fire final for June 18th with John Vincent | |
06/07/2019 | FIRE - FINAL | Partial Approval | 1) Remove door knobs from non-required exit doors. 2) Replace keyed lock on rear security gate with quarter turn lock. This is a required exit. 3) Add decal over main exit door. "these doors to remain unlocked..." 4) Mount extinguishers. 5) Obtain hot work operational permit. 6) Obtain compressed gasses operational permit. 7) Install ballards for compressed gases that are outside in parking lot. Install per IFC 312. 8) Add "no smoking" signs to exterior wall next to compressed gasses. 9) Add product signs "propane" and "oxygen" above tanks or on ballards. 10) Remove second lock from main exit door. Contact is Ryan 520-406-2956 |