Permit: T19CM01770

Parcel: 119220490


Addresses:

2741 S CASTLE DR

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
02/11/2020 BUILDING - FINAL Approved
02/07/2020 BUILDING - FINAL Denied 1- Shall post address on bldg.
2- Shall label all circuit breakers in the service panel.
3- Shall provide locking caps on the condenser refrigerant service ports .
4- Shall secure the liquid tight whip to the condenser.
5- Shall protect the insulation on the condenser line set.
6- Shall provide a water hammer arrestor for the dishwasher water supply.
7- Shall provide approved material for the Water Heater T & P drain and terminate it to the Mop Sink with a one inch air gap.
8- Water Heater has a leak.
9- Shall provide a Water Hammer Arrestor for the Clothes Washer.