Permit: T19CM01613

Parcel: 134241950


Addresses:

825 S LOYOLA AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/06/2019 ELECTRIC - SERVICE UPGRADE Approved Clearance TEP INCR.
07/16/2019 ELECTRIC - SERVICE UPGRADE Correction Required This is a new service panel and relocated outside the new addition.
2 ground rodsrequired to be a min of 6’ apart, these are 5’3" /-.
A gas bond is required as is a water pipe bond.
GEC to be #4 if copper.