Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2019 | ELECTRIC - SERVICE RELOCATION | Approved | Clearance TEP INCR. | |
| 07/26/2019 | ELECTRIC - SERVICE RELOCATION | Partial Approval | Need to bond water and gas lines before relo approval | |
| 07/23/2019 | ELECTRIC - SERVICE RELOCATION | Correction Required | Gas bond required. Water heater vent shall not be used as a gas bond chase for the bonding conductor. Bury the #4 GEC wires below grade for protection. |
|
| 07/19/2019 | ELECTRIC - SERVICE RELOCATION | Correction Required | Gas bond found on roof. Extra ground rod added to get six feet min distance apart. No water bond at inspection, required. |
|
| 07/17/2019 | ELECTRIC - SERVICE RELOCATION | Cancelled | IVRS - AP canceled | |
| 07/16/2019 | ELECTRIC - SERVICE RELOCATION | Not Applicable | ||
| 07/02/2019 | ELECTRIC - SERVICE RELOCATION | Not ready for Inspection | 1. Need appropriate size feeders, properly colorized, in mast. 2. Need mast supports on and under roof. 3. Caulk panel to building for waterproofing and seal home run hole in back of panel with foam after all wires are in place. |