Permit: T19CM01613

Parcel: 134241950


Addresses:

825 S LOYOLA AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
08/06/2019 ELECTRIC - SERVICE RELOCATION Approved Clearance TEP INCR.
07/26/2019 ELECTRIC - SERVICE RELOCATION Partial Approval Need to bond water and gas lines before relo approval
07/23/2019 ELECTRIC - SERVICE RELOCATION Correction Required Gas bond required.
Water heater vent shall not be used as a gas bond chase for the bonding conductor.
Bury the #4 GEC wires below grade for protection.
07/19/2019 ELECTRIC - SERVICE RELOCATION Correction Required Gas bond found on roof. Extra ground rod added to get six feet min distance apart.
No water bond at inspection, required.
07/17/2019 ELECTRIC - SERVICE RELOCATION Cancelled IVRS - AP canceled
07/16/2019 ELECTRIC - SERVICE RELOCATION Not Applicable
07/02/2019 ELECTRIC - SERVICE RELOCATION Not ready for Inspection 1. Need appropriate size feeders, properly colorized, in mast.
2. Need mast supports on and under roof.
3. Caulk panel to building for waterproofing and seal home run hole in back of panel with foam after all wires are in place.