Permit: T19CM01613

Parcel: 134241950


Addresses:

825 S LOYOLA AV

Inspection Status: Approved

Inspection History: RESIDENTIAL INTERMEDIATE

Date Description Inspector Results Comments
06/14/2019 RESIDENTIAL INTERMEDIATE Approved
06/12/2019 RESIDENTIAL INTERMEDIATE Not ready for Inspection Corrections not completed.
06/07/2019 RESIDENTIAL INTERMEDIATE Denied 1. Laundry vertical drain is too short. Needs to be 16” minimum.
2. New kitchen sink drain should be vented through roof or have an air admittance valve (steuder vent) installed.
3. Dryer electric outlet box is too small for outlet.
4. No electric or Hvac lines in place for mini splits yet.
5.electric intermediate is incomplete. Need all fixture boxes in place.