| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2019 | ELECTRIC - INTERMEDIATE | Approved | ||
| 05/18/2019 | ELECTRIC - INTERMEDIATE | Approved | 277/480V, 250AMP DG Disconnect to Existing SES, Conductors #300KCMIL, Neutral # 3AWG, Ground #3 AWG. LINE SIDE tap in Existing SES Approved, third party on site to run Hi-pot and Re-certify Gear. Verbal Clearance sent to TEP (RECN/DGL) @ 6:10 pm. |