Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T19CM01541

Parcel: 13707047A


Addresses:

101 W IRVINGTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T19CM01541

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2019 ELECTRIC - INTERMEDIATE Approved
05/18/2019 ELECTRIC - INTERMEDIATE Approved 277/480V, 250AMP DG Disconnect to Existing SES, Conductors #300KCMIL, Neutral # 3AWG, Ground #3 AWG. LINE SIDE tap in Existing SES Approved, third party on site to run Hi-pot and Re-certify Gear.
Verbal Clearance sent to TEP (RECN/DGL) @ 6:10 pm.