Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2019 | ELECTRIC - UFER | Approved | Note: move #4 rebar ufer to touch and run parallel to #4 continuous rebar that surrounds slab. Ok to pour |
|
| 04/15/2019 | ELECTRIC - UFER | Denied | Provide #4 Bare copper bonded to foundation rebar per plan |