Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T19CM01386
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2019 | ELECTRIC - RECONNECT | Approved | Clear rec for unit #5 | |
| 08/14/2019 | ELECTRIC - RECONNECT | Denied | 1. Correct double tapped circuits in sub panel. 2. Correct overfusing in sub panel. Note: To maintain the same number of circuits, a new sub panel may be needed. 3. Relocate smoke detectors per manufacturer’s specifications. 4. Strongly suggest that the outlet 10” from toilet bowl be gfi protected. 5. Screw water heater flue sections together and provide 1” clearance from flue to combustibles at roof. 6. Bond the water and gas lines to electric panel. |
|
| 03/04/2019 | ELECTRIC - RECONNECT | Correction Required | Water heater/ storage room in the rear of the building is in the process of being rebuilt without the requisite permit. Rafters have been replaced, walls have been rebuilt, and Durocher is installed on both sides. Roof sheeting is burnt, needs to be replace, and new B-vent does not have the requisite clearance. There are no combustion air vents in place, which will be required when door is installed. Owner was under the misunderstanding that only structural items require permitting. Ground rods still not exposed from previous corrections. | |
| 02/27/2019 | ELECTRIC - RECONNECT | Correction Required | 1-Obtain permit and pass inspections for addition in rear of home. 2-Expose or install ground rods for service. 3-Install smoke detector in bedroom. |