Permit: T19CM01386

Parcel: 11103206A

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T19CM01386

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
12/17/2019 ELECTRIC - RECONNECT Approved Clear rec for unit #5
08/14/2019 ELECTRIC - RECONNECT Denied 1. Correct double tapped circuits in sub panel.
2. Correct overfusing in sub panel.
Note: To maintain the same number of circuits, a new sub panel may be needed.
3. Relocate smoke detectors per manufacturer’s specifications.
4. Strongly suggest that the outlet 10” from toilet bowl be gfi protected.
5. Screw water heater flue sections together and provide 1” clearance from flue to combustibles at roof.
6. Bond the water and gas lines to electric panel.
03/04/2019 ELECTRIC - RECONNECT Correction Required Water heater/ storage room in the rear of the building is in the process of being rebuilt without the requisite permit. Rafters have been replaced, walls have been rebuilt, and Durocher is installed on both sides. Roof sheeting is burnt, needs to be replace, and new B-vent does not have the requisite clearance. There are no combustion air vents in place, which will be required when door is installed. Owner was under the misunderstanding that only structural items require permitting. Ground rods still not exposed from previous corrections.
02/27/2019 ELECTRIC - RECONNECT Correction Required 1-Obtain permit and pass inspections for addition in rear of home. 2-Expose or install ground rods for service.
3-Install smoke detector in bedroom.