Permit: T19CM01249

Parcel: 133170600

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T19CM01249

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/03/2019 ELECTRIC - FINAL Approved
05/01/2019 ELECTRIC - FINAL Denied Exhaust fan time clock cannot be switch operated within restroom or any area accessible to the public. Another failed inspection will result in a reinspection fe
04/25/2019 ELECTRIC - FINAL Not ready for Inspection Restroom exhaust fan to be interlocked with air conditioning or on time clock to run continuously during business hours
04/23/2019 ELECTRIC - FINAL Not ready for Inspection Call all finals at same time, provide sterilization report and air balance report to Robert Sherry prior to calling finals.
04/10/2019 ELECTRIC - FINAL Partial Approval ECO OK to clear