Permit: T19CM01180

Parcel: 136048090

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T19CM01180

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/15/2021 FIRE - ALARM FINAL Approved
01/14/2021 FIRE - ALARM FINAL Cancelled IVRS - RI canceled
01/07/2021 FIRE - ALARM FINAL Partial Approval -Submit as built plans
-Provide NFPA 72 ROC
-HVAC units did not shut down