Permit: T19CM01138

Parcel: 13824023J


Addresses:

1955 W VALENCIA RD


Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T19CM01138

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
10/25/2019 MECHANICAL - HOODS Approved
09/20/2019 MECHANICAL - HOODS Partial Approval 1- Fire Wrap is okay for both type 1 grease hoods. 2- Sensors hav3 no5 been installed at this time
09/18/2019 MECHANICAL - HOODS Denied 1- Shall remove the curb for the exhaust duct and provide a smoke test on the short drop through the trusses and provide the double layer fire wrap and then provide a smoke test on the connecting joint to the exhaust duct.
09/17/2019 MECHANICAL - HOODS Denied 1- Type 1 grease hood exhaust duct can not be fire caulked and screwed to the listed hood, this connection shall be welded.
2- The east hood has a leak on one of the welds.