Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T19CM01138
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2019 | MECHANICAL - HOODS | Approved | ||
09/20/2019 | MECHANICAL - HOODS | Partial Approval | 1- Fire Wrap is okay for both type 1 grease hoods. 2- Sensors hav3 no5 been installed at this time | |
09/18/2019 | MECHANICAL - HOODS | Denied | 1- Shall remove the curb for the exhaust duct and provide a smoke test on the short drop through the trusses and provide the double layer fire wrap and then provide a smoke test on the connecting joint to the exhaust duct. | |
09/17/2019 | MECHANICAL - HOODS | Denied | 1- Type 1 grease hood exhaust duct can not be fire caulked and screwed to the listed hood, this connection shall be welded. 2- The east hood has a leak on one of the welds. |