Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2019 | ELECTRIC - RECONNECT | Approved | Install carbon monoxide / smoke alarm in hallway before gas is turned on and electric final inspection. Recommend a gas pressure on house piping before gas is turned on. Clear rec |
|
| 03/25/2019 | ELECTRIC - RECONNECT | Denied | Work not complete, conditions are unsafe | |
| 02/19/2019 | ELECTRIC - RECONNECT | Not ready for Inspection | wiring and open boxes throughout house need to be made safe. Missing sub panel cover. Smoke alarms needed in each bedroom 3 foot away from supply air. Smoke and carbon alarm needed outside of sleeping area. Grounding and bonding cut at main panel, install ground rods and bond gas and water. |