Inspection Status: Approved
Inspection History: RESIDENTIAL INTERMEDIATE
Permit Number - T19CM01115
Inspection Description - RESIDENTIAL INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/10/2019 | RESIDENTIAL INTERMEDIATE | Approved | ||
05/09/2019 | RESIDENTIAL INTERMEDIATE | Not ready for Inspection | Unable to access for inspection | |
05/07/2019 | RESIDENTIAL INTERMEDIATE | Correction Required | 1-Rome’s is staples sideways throughout house; must be flat. 2-Provide nail protection for UF in masonry channels if less than 1-1/4” from surface. 3-Connect ufer to panel per IRC E3608.1 and E3610.1. 4-Electrical boxes are not extended through combustible surfaces throughout E3906.5). 5-Boxes not installed at West wall outside and Master Shower ceiling. |
|
05/06/2019 | RESIDENTIAL INTERMEDIATE | Not ready for Inspection | Electrical boxes not all installed and made up. No water in DWV. Gas piping not under test. Stopped inspection |