Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T19CM01102
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2020 | PLUMBING - ROUGH, SOIL | Approved | ||
| 04/09/2020 | PLUMBING - ROUGH, SOIL | Partial Approval | 1- Underground electric conduits and vacuum line to Island stations okay to cover. | |
| 03/18/2020 | PLUMBING - ROUGH, SOIL | Partial Approval | 1- Sand and Oil separator okay to cover. 2- Area drains and air lines okay to cover less the drain line from water and ice dispenser. |
|
| 03/16/2020 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | 1- Work is incomplete | |
| 01/31/2020 | PLUMBING - ROUGH, SOIL | Partial Approval | 1- (3) 4 inch vacuum line from bldg to canopy location is okay to cover. | |
| 11/07/2019 | PLUMBING - ROUGH, SOIL | Partial Approval | 1- Underground rough soil piping is okay to cover in the wash bay only. | |
| 11/06/2019 | PLUMBING - ROUGH, SOIL | Denied | 1- 2 inch Floor drain in restroom shall have a San tee in lieu of a combination tee wye for the trap arm. 2- 4 inch Floor sink minimum trap arm distance is two times the diameter of the pipe size. 3- Retest the system. |