Permit: T19CM01102

Parcel: 13813001E


Addresses:

5701 S 12TH AV


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T19CM01102

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2020 PLUMBING - ROUGH, SOIL Approved
04/09/2020 PLUMBING - ROUGH, SOIL Partial Approval 1- Underground electric conduits and vacuum line to Island stations okay to cover.
03/18/2020 PLUMBING - ROUGH, SOIL Partial Approval 1- Sand and Oil separator okay to cover.
2- Area drains and air lines okay to cover less the drain line from water and ice dispenser.
03/16/2020 PLUMBING - ROUGH, SOIL Not ready for Inspection 1- Work is incomplete
01/31/2020 PLUMBING - ROUGH, SOIL Partial Approval 1- (3) 4 inch vacuum line from bldg to canopy location is okay to cover.
11/07/2019 PLUMBING - ROUGH, SOIL Partial Approval 1- Underground rough soil piping is okay to cover in the wash bay only.
11/06/2019 PLUMBING - ROUGH, SOIL Denied 1- 2 inch Floor drain in restroom shall have a San tee in lieu of a combination tee wye for the trap arm.
2- 4 inch Floor sink minimum trap arm distance is two times the diameter of the pipe size.
3- Retest the system.