Permit: T19CM01078

Parcel: 110091480


Addresses:

2801 N SHERRY AV


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T19CM01078

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2019 ELECTRIC - SERVICE UPGRADE Approved Clearance TEP INCR.
04/26/2019 ELECTRIC - SERVICE UPGRADE Correction Required Metal conduit protecting Grounding Electrode Conductor needs to be boned at both ends, with a conductor equal in size to Grounding Electrode Conductor per NEC 250.64E1.
04/10/2019 ELECTRIC - SERVICE UPGRADE Correction Required Corrections from 3/27 have yet to be completed.
04/02/2019 ELECTRIC - SERVICE UPGRADE Correction Required Expose grounding electrode conductor and the connection of it to both ground
03/27/2019 ELECTRIC - SERVICE UPGRADE Not ready for Inspection Ground to be bonded to metal conduit sleeve