Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T19CM01078
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2019 | ELECTRIC - SERVICE UPGRADE | Approved | Clearance TEP INCR. | |
| 04/26/2019 | ELECTRIC - SERVICE UPGRADE | Correction Required | Metal conduit protecting Grounding Electrode Conductor needs to be boned at both ends, with a conductor equal in size to Grounding Electrode Conductor per NEC 250.64E1. | |
| 04/10/2019 | ELECTRIC - SERVICE UPGRADE | Correction Required | Corrections from 3/27 have yet to be completed. | |
| 04/02/2019 | ELECTRIC - SERVICE UPGRADE | Correction Required | Expose grounding electrode conductor and the connection of it to both ground | |
| 03/27/2019 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | Ground to be bonded to metal conduit sleeve |