Permit: T19CM01078

Parcel: 110091480


Addresses:

2801 N SHERRY AV


Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T19CM01078

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Approved

Date Description Inspector Results Comments
03/08/2019 EXCAVATION/LAYOUT REBAR & ZON Approved
03/06/2019 EXCAVATION/LAYOUT REBAR & ZON Partial Approval
03/05/2019 EXCAVATION/LAYOUT REBAR & ZON Correction Required Footing rebar to be 3” min distance from soil in any direction.
Vertical rebar to be 32” OC per plan details.
Plans unclear on whether a #4 top rebar is required in the footing.
Slab rebar grid shall be supported out of dirt and high enough for aggregate to encapsulate it during the pour.