Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T19CM01021
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/05/2021 | FIRE - FINAL | Approved | ||
11/17/2020 | FIRE - FINAL | Partial Approval | Following items from punch have been addressed at previous date. -Fire smoke damper labeling -Room identification -Door closures on rooms |
|
10/08/2020 | FIRE - FINAL | Partial Approval | TCO for floors 7 through 14 excluding the Roof because it is still under construction, pending the elevator inspection. Approved/Passed Sprinkler System Fire Alarm System including all guestroom/corridor smoke detectors and horn/strobes Fire Smoke Damper Function Mag Locks Door Holders Ceiling Mounted Exit Signs Punch List Items Need to test Two Way Communication Need Record of Completion Need to test door closures of hotel room doors when cardboard has been removed Room number identification needed for floors 7, 8 and 9 General labels for utility rooms, electrical rooms, lobbies etc. All FSD access doors need "Fire Smoke Damper" labels Elevators need to be commissioned by State Elevator Inspector Elevator Lobby key box and keys |