Permit: T19CM01021

Parcel: 12404100A


Addresses:

930 E 2ND ST


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T19CM01021

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/05/2021 FIRE - FINAL Approved
11/17/2020 FIRE - FINAL Partial Approval Following items from punch have been addressed at previous date.

-Fire smoke damper labeling
-Room identification
-Door closures on rooms
10/08/2020 FIRE - FINAL Partial Approval TCO for floors 7 through 14 excluding the Roof because it is still under construction, pending the elevator inspection.

Approved/Passed
Sprinkler System
Fire Alarm System including all guestroom/corridor smoke detectors and horn/strobes
Fire Smoke Damper Function
Mag Locks Door Holders
Ceiling Mounted Exit Signs

Punch List Items
Need to test Two Way Communication
Need Record of Completion
Need to test door closures of hotel room doors when cardboard has been removed
Room number identification needed for floors 7, 8 and 9
General labels for utility rooms, electrical rooms, lobbies etc.
All FSD access doors need "Fire Smoke Damper" labels
Elevators need to be commissioned by State Elevator Inspector
Elevator Lobby key box and keys