Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T19CM00948

Parcel: 130054350


Addresses:

2005 S NORTON AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/08/2019 ELECTRIC - FINAL Approved
03/22/2019 ELECTRIC - FINAL Correction Required 1- Service has been changed and is now connected; new service has no paper behind it, only plywood. 2-Electrical LB is buried in stucco, rendering it inaccessible. 3-Smoke detectors need to be installed in all three bedrooms, hallway and outside of separate bedroom. 4-Expose grounding electrode conductor and its connection to both ground rods.
02/20/2019 ELECTRIC - FINAL Not ready for Inspection Lock box code still does not work, nor is grounding secured. Obtain permit to cover new framing and wiring work taking place inside, along with any other work requiring a permit.
02/08/2019 ELECTRIC - FINAL Not ready for Inspection lockbox code left on message did not work. Secure grounding to house near panel