Inspection History Details
Inspection Status: Approved
Inspection History: RESIDENTIAL INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2019 | RESIDENTIAL INTERMEDIATE | Approved | ||
| 04/17/2019 | RESIDENTIAL INTERMEDIATE | Denied | Clear eco and please add 2061 to permit 1. Need to fire foam top plate penetrations in back bedroom. 2. 220V wire has mesh staples through it in kitchen, replace wire. 3. No pressure on gas line, need to fill line and retest. 4. Nail boca plates completely over condensate drain lines in living room. 5. Provide nail protection at potable water lines in kitchen. |