Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T19CM00820
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/24/2019 | ELECTRIC - UNDERGROUND | Approved | APPROVED PER 2090 APPROVAL | |
06/21/2019 | ELECTRIC - UNDERGROUND | Not ready for Inspection | Underground electric to be a minimum 18 inches deep, or provide 2 inch concrete encasement. | |
05/31/2019 | ELECTRIC - UNDERGROUND | Not ready for Inspection | Pothole electric conduit to verify minimum 18" below grade. | |
05/20/2019 | ELECTRIC - UNDERGROUND | Not ready for Inspection | Already covered; uncover to verify burial depth and install tracer wire. |