Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/21/2020 MECHANICAL - FINAL Approved
03/20/2019 MECHANICAL - FINAL Not ready for Inspection new electrical panel which is part of the drawings does not have any grounding, please add 2 ground rods 6 foot apart and bond gas and water. Also panel is not labeled and improperly wired. The only breaker that is labeled is for the air-conditioner is oversized see max fuse size. Didn’t see disconnect within site of condenser. Also need to provide a ladder to see work done on the roof, and make sure evaporative cooler was capped correctly