Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T19CM00523
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/24/2019 | MECHANICAL - FINAL | Approved | ||
09/23/2019 | MECHANICAL - FINAL | Denied | Shall provide a tight band on the top section of fire wrap inside the the existing partial shaft every 10.5 inches. | |
09/20/2019 | MECHANICAL - FINAL | Partial Approval | 1- Type 1 Grease Hood smoke test was performed and okay | |
09/19/2019 | MECHANICAL - FINAL | Denied | 1- Shall provide a clean out on the Grease Exhaust Duct. |