Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T19CM00523
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/24/2019 | PLUMBING - FINAL | Approved | ||
09/20/2019 | PLUMBING - FINAL | Denied | 1- Shall locate the Accessible water closet side wall clearance to be 16 to 18 inches center. 2- Shall locate the Accessible lavatory a minimum of 15 inches from side wall. 3- Shall provide a watts 1022 in line vacuum breaker for the Tea Dispenser supply line |