Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T19CM00507
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2019 | ELECTRIC - INTERMEDIATE | Approved | ||
| 04/03/2019 | ELECTRIC - INTERMEDIATE | Correction Required | Can see at final. GEC from UFER cannot be attached to the isolated neutral buss. Attach to th the bonded ground buss as required. Take the bonding leg off the Nuetral buss and remove entirely or install on th Ground buss which is bonded to the can. |
|
| 03/27/2019 | ELECTRIC - INTERMEDIATE | Correction Required | Need truss calc’s Approved for any inspections |