Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 02/04/2019 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
|
| 01/28/2019 |
PLUMBING - GAS PRESSURE TEST |
|
Correction Required |
Commercial gas line at Zero. Test not holding. Over 500 cu/ft. Pie R sq x length of line divided by 500. 1/2 hour per 500 cu/ft req as time for test to hold. IFGC |