Inspection History Details
Inspection Status: Denied
Inspection History: BUILDING - FINAL
Permit Number - T19CM00486
Inspection Description - BUILDING - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/31/2019 | BUILDING - FINAL | Denied | 1- Shall provide a 1022 in line backflow preventer devise at the soap dispenser at Mop Sink. 2- Shall locate the the Accessible signage for restrooms on the latch side of doors. 3- Shall provide 10 seconds of flow on accessible lavatories 4- Shall provide water hammer arrestors for the pressure assist water closets. 5- Shall provide a label on the ceiling tile the location of the Anzul Valve. |
|
07/31/2019 | BUILDING - FINAL | Approved | 1-All corrections have been made, recommend for C of O. | |
07/26/2019 | BUILDING - FINAL | Partial Approval | Pending other inspections. |