Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2019 | PLUMBING - GAS PRESSURE TEST | Approved | ||
| 01/25/2019 | PLUMBING - GAS PRESSURE TEST | Denied | 1- Shall provide double wall flu vent on water heater when located in a exterior location. 2- Shall provide gas bond. 3- Shall provide combustion air openings on water heater enclosure. 4- Shall annotate all gas appliances on plan. |
|
| 01/23/2019 | PLUMBING - GAS PRESSURE TEST | Denied | .5 lbs of pressure at inspection. Check and repair leaks as needed. |