Permit: T19CM00349

Parcel: 123051740


Addresses:

1825 N NORTON AV


Inspection Status: Correction Required

Inspection History: PLUMBING - FINAL

Permit Number - T19CM00349

Inspection Description - PLUMBING - FINAL

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/08/2019 PLUMBING - FINAL Correction Required Water Heater. P&T drain line to be 3/4 inch interior diameter and no PVC.
Drip req on gas supply line .
Thimble at ceiling req for B vent clearance per manufacturer.
3 Tec screws req at vent connector to B vent and B vent to water heater draft hood.
Combustion air required at door. 100 sq in within 12 in of the ceiling and within 12 in of the floor.