Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2019 | ELECTRIC - FINAL | Approved | Clear rec. | |
| 04/01/2019 | ELECTRIC - FINAL | Partial Approval | All smokies and carbons in place, confirmed Gas and water bond with continuity test. Identify circuit breakers in Main and Sub Panels. Provide KO seal in main panel, cover plate for laundry switch. | |
| 01/11/2019 | ELECTRIC - FINAL | Denied | 1. Correct all deficiencies in main panel- several double taps, missing bushing in knock out, Maine and circuit ground connections. 2. Correct double tap in interior sub panel. Evaluate and correct, as needed, what appears to be unpermitted wiring. 3. Need CO detector in hallway. Note: Front door was unlocked and ajar at arrival at 12:20. |