Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2019 | FIRE - ALARM FINAL | Approved | ||
| 10/09/2019 | FIRE - ALARM FINAL | Partial Approval | -add notification in kitchen and walk in cooler -increase sound level of horns in basement storage and office areas -have ground faults register on panels -provide NFPA 72 ROC upon completion -label alarm panel and electrical panel power circuit location -lockout power supply breaker -tamper 1 of rider 2 did not report to panel -submit as-built plans prior to final |