Permit: T19CM00123

Parcel: 128010040

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T19CM00123

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/16/2019 FIRE - ALARM FINAL Approved
10/09/2019 FIRE - ALARM FINAL Partial Approval -add notification in kitchen and walk in cooler
-increase sound level of horns in basement storage and office areas
-have ground faults register on panels
-provide NFPA 72 ROC upon completion
-label alarm panel and electrical panel power circuit location
-lockout power supply breaker
-tamper 1 of rider 2 did not report to panel
-submit as-built plans prior to final