Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/11/2019 |
MECHANICAL - FINAL |
|
Approved |
Pending balance report approval. |
| 10/09/2019 |
MECHANICAL - FINAL |
|
Partial Approval |
Provide approved air balance report, provide smoke containment test at type one hoods, provide approve gasket at type one hood exhaust termination, provide proper termination of condensate drain at Mini split system |