Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T19CM00029
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2019 | FRAMING | Approved | ||
04/05/2019 | FRAMING | Partial Approval | Connect gas bond Block between upper/lower combustion wall vents in garage Block all duct boots on 1st and 2nd floor Boca plate abs line on west dinning room wall 3 point bearing floor trusses not bearing on wall between kitchen and garage need RFI from engineer to address this issue Fire foam plumbing and abs penetration between garage and first floor bathroom Secure toilet flange in both upstairs bathroom 2x backing at tub/shower edge in 2nd bathroom Wire exhaust fan in laundry room Shower not under test in master bathroom |