Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2019 | PLUMBING - FINAL | Approved | ||
| 03/07/2019 | PLUMBING - FINAL | Denied | 1- Shall provide the required test gage 15 lbs max with 1/10th increments when providing a test. 2- Shall provide a minimum of 5 feet of B- vent for the water heater from the draft collar to the vent cap. 3- Shall extend and terminate the water heater T & P valve 6 inches above sub grade. |