Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
Permit Number - T19BU00039
Inspection Description - POOL/SPA ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2019 | POOL/SPA ELECTRIC | Approved | ||
07/24/2019 | POOL/SPA ELECTRIC | Denied | Electrical circuit over fused. #10AWG CANNOT be fused at 50AMPS. Have inspected and called this out multiple times, recommend inspection fee if work incomplete upon next inspection. | |
06/26/2019 | POOL/SPA ELECTRIC | Denied | Sub Panel Conductors Are undersized. Breaker is fused at 50AMPs which requires a minimum #8 sized Conductors. Sub-Panel Needs to be identified at Main Service. All Electrical shall be complete prior to Pool Final. |