Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 08/06/2019 |
POOL/SPA ELECTRIC |
|
Approved |
|
| 07/24/2019 |
POOL/SPA ELECTRIC |
|
Denied |
Electrical circuit over fused. #10AWG CANNOT be fused at 50AMPS. Have inspected and called this out multiple times, recommend inspection fee if work incomplete upon next inspection. |
| 06/26/2019 |
POOL/SPA ELECTRIC |
|
Denied |
Sub Panel Conductors Are undersized. Breaker is fused at 50AMPs which requires a minimum #8 sized Conductors. Sub-Panel Needs to be identified at Main Service. All Electrical shall be complete prior to Pool Final. |