Inspection Status: Not Ready
Inspection History: COT - ENGR - Signage Final
| Date |
Description |
Inspector |
Results |
Comments |
| 10/27/2022 |
COT - ENGR - Signage Final |
|
Not Ready |
|
| 06/21/2018 |
COT - ENGR - Signage Final |
ACONNOR |
Approved |
Entered by ACONNOR1 - TOTAL $736.12 |
| 05/29/2018 |
COT - ENGR - Signage Final |
hthrall |
Partial Approval |
Entered by HTHRALL1 - RE: new wall /window signs
AT: 3699 E Broadway, Target
Zoning: C-2 (rezoning - condition, no exemptions for signs visible to residential)
Permit: T18OT00564
Facade renovation review: T17CM9383 (completed to now include exterior renovation)
Sign Code determination: T17SA00436
Reviewer: H. Thrall
Sign area and change copy proposal within code, meets rezoning conditions.
The following corrections to the plans are needed:
1) Provide mounting details for:
A) Sign "A" individual letter and logo signage at 225 square feet sign area. (ie. size number of bolts and number of penetrations per letter to wall surface) Response may require engineered plans and special inspection.
2) Electrical: NEC 600
A) Acknowledged a "lockable disconnect" noted on plans. Clarify - separate from required shut off switch locations to signs? (all signs)
3) Outdoor Lighting Code: Ch. 4
A) provide timer, indicate where located - notation or diagram is fine - all signs
4) Note - Target has a freestanding sign along Broadway at this location. Please clarify if there are any desired plans of action for this sign and add to plans if applicable.
|