Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2019 | FIRE - ALARM FINAL | Approved | ||
| 11/19/2019 | FIRE - ALARM FINAL | Partial Approval | change the descritptions for the flow switches Correct the tamper switches so that they are properly labeled and work correctly add notification devices to the 4 showers, womens and mens locker rooms, phone rooms and the wellness room Confirm that all candella match the fire alarm drawings Primary tested the fire alarm for TCO to fixture. Still need to test the rest of the fire alarm system. Work at getting the ghost out of the fire alarm system and the notification devices. |