Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T18FC00900
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/27/2018 | FIRE - ALARM FINAL | Approved | ||
12/20/2018 | FIRE - ALARM FINAL | Partial Approval | Bathrooms need to have strobe only's per the plans (4) and they all need to be raised so that they are 80" to the bottom of the lense from the Finished Floor Horn Strobe outside of the Boarder Patrol area needs to be raised so that the lense is 80" above the finished floor Manual pull station, TIA Secure/ Holding and Boarder Patrol area all need to be adjusted so that they are 42-48" operable parts above finished floor Need to label the power supply with the disconnecting means Need to add RED Lock out on Breaker that reads FIRE ALARM CIRCUIT Need to have the cap placed on the gutter box above the FACP Need to test the fire alarm for proper operation and synchronization. |