Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date |
Description |
Inspector |
Results |
Comments |
| 07/03/2019 |
FIRE SPKLR - OH PIPING & HYDRO |
|
Approved |
|
| 03/04/2019 |
FIRE SPKLR - OH PIPING & HYDRO |
|
Approved |
207 & 209 PSI on the gauges. The west building design has completely been altered since the plans that we approved were issued with a permit. Need to have ASBUILT drawings prior to final. Some of the pipe is right on the heat registers need to move away. Three-Four heads were covered in foam and need to be replaced. |