Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T18FC00861

Parcel: 10504136C


Addresses:

575 E RIVER RD

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
12/17/2018 FIRE - ALARM FINAL Approved
12/07/2018 FIRE - ALARM FINAL Partial Approval Add 4 notification devices to the shared offices
Lower the manual pull station 42-48 operable parts
Requires 75 dBA throughout the faility
-Owner to provide documentation showing that fire alarm was approved in 1980's to get out of doing the 75 dBA.