Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2018 | FIRE - ALARM FINAL | Approved | ||
| 12/07/2018 | FIRE - ALARM FINAL | Partial Approval | Add 4 notification devices to the shared offices Lower the manual pull station 42-48 operable parts Requires 75 dBA throughout the faility -Owner to provide documentation showing that fire alarm was approved in 1980's to get out of doing the 75 dBA. |