Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T18FC00651
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/13/2019 | FIRE - ALARM FINAL | Approved | Per Chris Basaldua | |
02/07/2019 | FIRE - ALARM FINAL | Partial Approval | 1. Need NFPA 72 form. 2. Still need as builts. |
|
01/28/2019 | FIRE - ALARM FINAL | Partial Approval | 1. need as builts/revision submitted. rooms have changed on the NW side of bldg. 2. need to test RTU ducts, ground fault, smoke above FACP. 3. need to verify AC power to FACP and burg is OK. both on same/one circuit. 4. need 72/ROC. 5. need document from Bosch stating it is OK to mount annunciator to front panel of FACP with screws without voiding its listing. 6. add all info inside FACP cover. acct #, panel, circuit breaker, etc... 7. could not verify signals after testing. if unable to provide report from central station on todays test, all devices shall be tested again. |