Permit: T18FC00614

Parcel: 137055590

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T18FC00614

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/13/2018 FIRE SPKLR - FINAL Approved Final done by CB
11/09/2018 FIRE SPKLR - FINAL Partial Approval MAIN DRAIN TEST 75-55-80
NEEDS THE FOLLOWING:
-add lockout to fire bell
-need knox fdc plugs
-need spare heads in box
-add PRV to riser