Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T18FC00577
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/21/2018 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
09/14/2018 | FIRE - KITCHEN EXH HOOD FINAL | Partial Approval | PA. Trip test passed. Not OK/approved to cook or use appliances. Still need the following before full approval is given. 1) Need as-builts. -correct linup needs to be on plans. -plans and calcs missing one drop nozzle under salamandar. -Also missing 36 plenum nozzles on plans and calcs. Unsure if these nozzles need to be included with calcs. Will verify with our plan reviewer. -incorrect part numbers on plans for duct nozzles and plenum nozzles. -I need to verify the tamper switch supervision requirement. Currently it is not supervised by the FACP. It is only locally supervised by the hood. If water is turned off, electric and gas shut off as a safeguard. -static 60psi, operating 52psi |