Permit: T18FC00538

Parcel: 121093580


Addresses:

2121 N CRAYCROFT RD


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T18FC00538

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/19/2019 FIRE - ALARM FINAL Approved
03/06/2019 FIRE - ALARM FINAL Partial Approval Asbuilt were approved
02/21/2019 FIRE - ALARM FINAL Partial Approval -add horn/strobe in area "A" that is missing.
-submit as-builts, pay fees.
01/17/2019 FIRE - ALARM FINAL Partial Approval 1. all the wet system side is approved. flows, tampers, smoke above panel, and pull station in facp room.
2. fire door drop approved.
3. Db level not meeting code in several rooms. Acura will verify all the rooms needing horns. will submit revision. will need to test all areas again.
4. add notification in the outside courtyard.