Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T18FC00510
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/26/2019 | FIRE - ALARM FINAL | Approved | Phase 3 complete | |
11/14/2018 | FIRE - ALARM FINAL | Partial Approval | Partial for Phase 2 | |
08/23/2018 | FIRE - ALARM FINAL | Partial Approval | Phase 1 old notification is at 75 and needs to be at the 80 minimum of new code. Code in 2002 required them to be at 90 inches, approved worng by the state FM. They have one more inspection, if it goes to phase three they will need to pay fees |