Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T18FC00474
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2018 | FIRE - ALARM FINAL | Approved | ||
| 07/19/2018 | FIRE - ALARM FINAL | Approved | fire alarm is monitoring the shut down of the HVAC but it is not shutting the installed fire smoke dampers. |