Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T18FC00449
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2018 | FIRE - ALARM FINAL | Approved | ||
| 06/11/2018 | FIRE - ALARM FINAL | Partial Approval | Trace 520-256-5229 Fire alarm breaker requires a red lock out. FACP needs to be labeled "Fire Sprinkler Monitoring Panel" Transformer for the cellular communicator needs to have a UL listed enclosure and lock Submit asbuilt drawings shpwing FACP changes. Tested the smoke detector, manual pull station, water flow and tamper. All signals sent to the monitoring. |