Permit: T18FC00423

Parcel: 126122500


Addresses:

4575 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T18FC00423

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/15/2019 FIRE - ALARM FINAL Approved
07/09/2019 FIRE - ALARM FINAL Partial Approval verified that new back flow valve tamper switches communicate with panel.

1. Need completed as-built plans
07/03/2019 FIRE - ALARM FINAL Denied No one on site.
06/13/2019 FIRE - ALARM FINAL Partial Approval 1. Submit as-built plans
06/03/2019 FIRE - ALARM FINAL Denied 1. Could not verify mag locks on egress doors (devices had no power)
2. Signals did not transmit to monitoring station
3. Submit as-built plans for additions to alarm system
4. Provide NFPA 72 ROC paperwork
5. Tested all smokes, pull stations and duct detectors.