Inspection History Details
Inspection Status: Canceled
Inspection History: COT - FCON - Hood System - Final
Permit Number - T18FC00381
Inspection Description - COT - FCON - Hood System - Final
Inspection Status - Canceled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/28/2021 | COT - FCON - Hood System - Final | Y MONTIJO | Cancelled | Entered by YMONTIJ1 - RE-OPEN PERMIT |
01/15/2019 | COT - FCON - Hood System - Final | jvincent | Denied | Entered by JVINCEN1 - -nozzle over range (245), too low. its at 37" -need ITM report. -nozzle over fryer too high. Currently 290 nozzle > 16" -need revision/as builts. |